Publication GMSI10-UM008D-EN-P - August 2010

38

XM-362 Module Sensor Wiring

The XM-362 accepts inputs only from Thermocouples. All six input channels
are electrically isolated from each other and from circuit power and ground.
The isolation provided is up to 250 V.

Figure 2.32 shows the wiring of thermocouples to the terminal base unit of the
XM-362 module.

Figure 2.32 Thermocouple to XM-362 Wiring

IMPORTANT

With all the cable shields connected (six individual input
cables and six output cables), there are not enough chassis
terminals for each shield. Therefore, the cable shields
should be paired as depicted in the following illustrations.
Recommended practice is to use a crimp ferrule.
Alternatively, you can use a separate grounding block
mounted next to the module.

TYPICAL WIRING FOR THERMOCOUPLES
TO XM-362 TEMPERATURE MODULE

30

29

IN 5+

IN 5 -

grounded thermocouple

grounded thermocouple

+

-

28

27

25
26

+

-

IN 6+

IN 6 -

within 250V

-

+

ungrounded thermocouple

IN 4+

IN 4 -

37
38

Power
Supply

24V dc

+

-

within 250V

ATTENTION

You may ground the cable shield at either end of the cable.
Do not ground the shield at both ends. When using an
ungrounded thermocouple, the shield must be connected
to ground at the module end.