Connecting the power supply – Rockwell Automation 1440-TTC06-00RE XM-362 Temperature Module User Manual

Page 29

Advertising
background image

Publication GMSI10-UM008D-EN-P - August 2010

21

Connecting the Power Supply

The power supply to the module is nominally 24V dc (±10%) and must be a
Class 2 rated circuit.

Wire the DC-input power supply to the terminal base unit as shown in Figure
2.8.

Figure 2.8 DC Input Power Supply Connections

40

Common

Internally DC-coupled to circuit ground

41

Chassis

Connection to DIN rail ground spring or panel mounting hole

42

Chassis

Connection to DIN rail ground spring or panel mounting hole

43

Chassis

Connection to DIN rail ground spring or panel mounting hole

44

CAN_High

DeviceNet bus connection, high differential (white wire)

45

CAN_Low

DeviceNet bus connection, low differential (blue wire)

46

CAN Shield

DeviceNet bus connection to chassis ground (bare wire)

47

DNet V (+)

DeviceNet bus power input, positive side (red wire)

48

DNet V (-)

DeviceNet bus power input, negative side (black wire)

49

4-20 mA 4 (-)

4-20 mA output 4, negative side

50

4-20 mA 5 (-)

4-20 mA output 5, negative side

51

4-20 mA 6 (-)

4-20 mA output 6, negative side

Terminal Block Assignments