Parameter object (class id 0fh), Class attributes, Instances – Rockwell Automation 1440-TTC06-00RE XM-362 Temperature Module User Manual

Page 105: Class attributes instances, Parameter object (class id 0f

Advertising
background image

Publication GMSI10-UM008D-EN-P - August 2010

97

Parameter Object
(Class ID 0F

H

)

The Parameter Object provides the interface to the XM-361 and XM-362
configuration data. There are 38 Parameter Object instances implemented in
the XM-361 and XM-362 modules.

Parameter Object instances 1-22 and 31-36 are implemented to provide an
alternate method of setting the configuration parameters with EPATH or
ENGUNIT data types. And Parameter Object instances 23 and 24 provide an
alternate method of setting the Produced Connection Size and Produced
Connection Path attributes for the Poll Connection because these attributes
can be difficult to get/set directly through the Connection Object.

Class Attributes

Instances

There are 38 instances of this object.

Table C.23 Parameter Object Class Attributes

Attr ID

Access
Rule

Name Data

Type

Description

Semantics

2

Get

Max Instance

UINT

Maximum instance
number of an object in
this class.

Total number of parameter
object instances.

8

Get

Parameter Class
Descriptor

WORD

Bits that describe the
parameter.

Bit 0 Supports Parameter
Instances
Bit 1 Supports Full Attrib.
Bit 2 Must do non-volatile store
Bit 3 Params in non-volatile

9

Get

Config.
Assembly
Instance

UINT

Set to 0

Table C.24 Parameter Object Instances

Instance

Read
Only

Name

Data Type

Valid Values

Default Value

1

Yes

Measurement Unit Channel 1

USINT

0 = Deg C
1 = Deg F

0

2

Yes

Measurement Unit Channel 2

USINT

0 = Deg C
1 = Deg F

0

3

Yes

Measurement Unit Channel 3

USINT

0 = Deg C
1 = Deg F

0

4

Yes

Measurement Unit Channel 4

USINT

0 = Deg C
1 = Deg F

0