Terminal block assignments – Rockwell Automation 1440-TTC06-00RE XM-362 Temperature Module User Manual

Page 26

Advertising
background image

Publication GMSI10-UM008D-EN-P - August 2010

18

Figure 2.7 XM-944 Terminal Base Unit

Terminal Block Assignments

The terminal block assignments and descriptions for the XM-361 and XM-362
modules are shown below.

ATTENTION

The terminal block assignments are different for different
XM modules. The following table applies only to the
Temperature modules. Refer to the installation instructions
for the specific XM module for its terminal assignments.

WARNING

EXPLOSION HAZARD

Do not disconnect equipment unless power has been
removed or the area is known to be nonhazardous.
Do not disconnect connections to this equipment unless
power has been removed or the area is known to be
nonhazardous. Secure any external connections that mate
to this equipment by using screws, sliding latches, threaded
connectors, or other means provided with this product.

XM-944, Cat. No. 1440-TB-E

Terminal Block Assignments

Name

No.

XM-361

XM-362

Description

0

Chassis

Connection to DIN rail ground spring or panel mounting hole

1

Chassis

Connection to DIN rail ground spring or panel mounting hole

2

Chassis

Connection to DIN rail ground spring or panel mounting hole

3

RTD 1 (+)

No Connection

Constant current is sourced to the RTD
Positive voltage across the RTD is measured here
Redundant terminal should remain unterminated

4

RTD 1 (+)

No Connection