Data Parameters

The Data parameters are used to view the measured values of the input
channels and the 4–20 mA outputs, as well as to monitor the status of the
channels, alarms, and relays.

Channel Data Parameters

TIP

To view all the data parameters in the XM Serial
Configuration Utility, click the View Data tab.

Channel Data Parameters

Parameter Name

Description

Values/Comments

Channel Status

States whether a fault exists on the associated
channel. If a fault exists, the measurement and rate
of change values may not be accurate.

Possible status values: No Fault

Fault

Shows the current measurement value for the
channel.

Important: Channel 6 data values are
not available if the Enable relay
reset switch terminals
is enabled.
(Refer to General Parameters on page
48.) The Channel 6 measurement
Value will display "Open" if the
measurement value is <0.5, or
"Closed" if the measurement value is

≥ 0.5.

Shows the current rate of change value for the
channel.

Difference

Shows the current difference value for the channel.
This value is calculated by subtracting the previous
channel's measurement from this channel’s
measurement.

Cold Junction Temperature (XM
Serial Configuration Utility only)

Shows the temperature at the module’s terminal
block junction.

Cold Junction Status (XM Serial
Configuration Utility only)

Shows the cold junction status.

Possible status values: Overrange

Underrange
No Fault

XM Configuration
Utility

EDS File

Value

Measurement
Value

XM Configuration
Utility

EDS File

Rate

Rate of
Change