Instance attributes – Rockwell Automation 1440-TTC06-00RE XM-362 Temperature Module User Manual

Page 107

Advertising
background image

Publication GMSI10-UM008D-EN-P - August 2010

99

1

The Poll Connection Produced Connection Path and Size parameters cannot be set while the Poll Connection is
already established with a master/scanner. Attempting to do so will result in an "Object State Conflict" error
(error code 0XC). These Parameter instances are a little more flexible than the actual Connection Object
attributed because they can be set while the connection is in the NON-EXISTENT state (before the
master/scanner allocates the connection).

Instance Attributes

26

Yes

Channel 2 Difference

REAL

Channel 2 - Channel 1

27

Yes

Channel 3 Difference

REAL

Channel 3 - Channel 2

28

Yes

Channel 4 Difference

REAL

Channel 4 - Channel 3

29

Yes

Channel 5 Difference

REAL

Channel 5 - Channel 4

30

Yes

Channel 6 Difference

REAL

Channel 6 - Channel 5

31

No

4-20 mA Output 1
Measurement Identifier

USINT

0 = Measurement Value
1 = Difference Value

0

32

No

4-20 mA Output 2
Measurement Identifier

USINT

0 = Measurement Value
1 = Difference Value

0

33

No

4-20 mA Output 3
Measurement Identifier

USINT

0 = Measurement Value
1 = Difference Value

0

34

No

4-20 mA Output 4
Measurement Identifier

USINT

0 = Measurement Value
1 = Difference Value

0

35

No

4-20 mA Output 5
Measurement Identifier

USINT

0 = Measurement Value
1 = Difference Value

0

36

No

4-20 mA Output 6
Measurement Identifier

USINT

0 = Measurement Value
1 = Difference Value

0

37

No

Enable Relay Reset Switch

BOOL

0 = Disabled
1 = Enabled

0

38

No

Sensor OOR Allowance

REAL

0-5%

0.0

Table C.24 Parameter Object Instances

Instance

Read
Only

Name

Data Type

Valid Values

Default Value

Table C.25 Parameter Object Instance Attributes

Attr ID

Access
Rule

Name Data

Type

Description

Semantics

1

Set

Parameter
Value

Actual value of parameter See Table C.24 for a list of valid

values for each instance.

2

Get

Link Path Size

USINT

Size of Link Path

0 (These Parameter instances do
not link directly to another
object attribute.)

Advertising