Chapter 5

Motion Logix Integration

20. Exit Ultraware.

Configure Your Logix DeviceNet Module

Follow these steps to configure your Logix DeviceNet module.

Commission an Out-of-Box DeviceNet Module

1. Be sure that all of your CompactLogix controller modules (processor, I/O modules, scanner,

and power supplies) are properly seated on the DIN rail and that the bus interconnect is
properly slid over to the previous module and seated.

2. Apply power to the CompactLogix power supply and wait for the components to power up.

3. Connect your workstation to the CompactLogix controller.

If you are using a serial connection, make sure that you have connected the 1756-CP3 (or
similar) cable between your workstation and one of the 9-pin serial ports on the controller.

If you are using an Ethernet connection, make sure that you have connected a twisted-pair
cable between your workstation and the controller’s RJ45 connection.

4. Create a communication driver in RSLinx Classic software. If needed, refer to the

CompactLogix System Quick Start Manual, publication

IASIMP-QS001

.

5. Open the DeviceNet Node Commissioning Tool by choosing Start>Programs>Rockwell

Software>RSNetWorx>DeviceNet Node Commissioning Tool.

IMPORTANT

Repeat all steps in this section for additional Ultra3000 servo drives.

IMPORTANT

This section is for commissioning an out-of-box DeviceNet scanner module. You do not
need to perform the steps in this section if your scanner is already configured.