Powers MM430 Master Tempering Valves User Manual

Technical instructions

Advertising
background image

MM430_For_PS-Sheet_Test_1.pdf

Page 1

09/14/2007

The Hydroguard

®

XP LFMM430 series is a temperature actuated

mixing valve designed for use in hot water distribution systems, in

compliance with ASSE 1017.

Maximum Operating Pressure ............. 125 psi (861 kPa)
Maximum Hot Water Temperature .......200°F (93°C)
Minimum Hot Water Supply Temp ....... 5°F (3°C) Above Set-Point*
Temp. Adjustment Ranges
** Standard:........................................ 90 - 160°F (32 - 71°C)

Low: ..................................................... 60 - 90°F (16 - 32 C)

Hot Water Inlet Temperature Range .....120 -180°F (49 - 82°C)
Cold Water Inlet Temperature Range ... 40 - 80°F (4 - 27°C)
Listing......................................................... ASSE 1017
Certified .................................................... CSA B125

* With Equal Pressure

**

Low limit cannot be less than the cold water temperature.

For best operation, hot water should be at least 5°F (3°C)

above desired set point.

Specifications

n

HYDROGUARD

®

XP

Master Tempering Valves

Series LFMM430

Technical Instructions

IS-P-MM430

Advanced Thermal Activation

WARNING

!

Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use infor-

mation can result in death, serious personal injury,

property damage, or damage to the equipment.
Keep this Manual for future reference.

You are required to consult the local building and plumbing

codes prior to installation. If the information in this manual is

not consistent with local building or plumbing codes, the local

codes should be followed. Inquire with governing authorities for

additional local requirements.

WARNING

!

WARNING

!

Flush all pipes thoroughly before installation. Installation and

field adjustment are the responsibility of the installer.

NOTICE

Description

n

WARNING

!

Need for Periodic Inspection and Yearly Maintenance:

Periodic inspection and yearly maintenance by a licensed con-

tractor is required. Corrosive water conditions and/or unauthor-

ized adjustments or repair could render the valve ineffective for

service intended. Regular checking and cleaning of the valve’s

internal components and check stops helps assure maximum

life and proper product function. Frequency of cleaning and

inspection depends upon local water conditions.

FAILURE TO COMPLY WITH PROPER INSTALLATION AND

MAINTENANCE INSTRUCTIONS COULD CONTRIBUTE TO THE

VALVE FAILURE.
This Hot Water Master Tempering Valves cannot be used for

tempering water temperature at fixtures. Severe bodily injury

(i.e., scalding or chilling) and/or death may result depending

upon system water pressure changes and/or supply water

temperature changes. ASSE standard 1016, 1069 or 1070 listed

devices should be used at fixtures to prevent possible injury.
These Hot Water Tempering Valves are designed to be

installed at or near the boiler or water heater. They are not

designed to compensate for system pressure fluctuations and

should not be used where ASSE standard 1016, 1069 or 1070

devices are required. These valves should never be used to

provide “anti-scald” or “anti-chill” service.
The components of the system must be of materials with a

construction capable of withstanding the high limit output tem-

peratures of the water heating source.