To set up the mainline, Managing concurrent zones – Baseline Systems BaseStation 3200 User Manual

Page 69

Advertising
background image

BaseStation 3200 Advanced Irrigation Controller Manual

the zone will be marked as good and watering will continue. If the variance is out of limit, then the zone

will be marked as a failure and shut down. This method allows watering to continue almost without

interruption, while isolating the faulty zone or zones.

To set up the mainline

1. Turn the dial to the Flow Menu position.
2. Press the NEXT button to select Mainline Setup, and then press the ENTR button. The Mainline Setup screen

displays.

3. In the Mainline Number field, press the + or button to select the number of the mainline that you want to

set up.

4. Press the NEXT button to go to the Design Flow GPM field, and then press the + button to enter the amount

of flow in gallons per minute (GPM) that is allowed through the mainline for the irrigation system.
Note: Press and hold the + button or the button to rapidly increase or decrease the number in the field.

5. Press the NEXT button to go to the Pipe Fill Time field, and then press the + button to enter the amount of

time that it takes to fill the pipe and achieve a steady flow rate after a valve change.

6. Press the NEXT button to go to the Limit by Flow field. If you want the controller to use the mainline design

flow to determine how many zones can run concurrently, press the + button to enter Y (yes).

7. Press the NEXT button to go to the High Alarm field. If you want to set an alarm for a high flow variance

condition, press the + button to enter a percentage in the field.
Example: If the expected flow is 50 GPM, and the High Alarm field is set to 10%, then the acceptable flow

range is up to 55 GPM (10% of 50 GPM is 5 GPM). A flow amount over 55 GPM would trigger the high flow

variance alarm.

8. Press the NEXT button to go to the High Shutdown field. If you want

the system to shut down when a high flow is detected, press the +

button to enter Y (yes).

9. Press the NEXT button to go to the Low Alarm field. If you want to set

an alarm for a low flow variance condition, press the + button to enter

a percentage in the field.
Example: If the expected flow is 50 GPM, and the Low Alarm field is set

to 10%, then the flow can decrease to 45 GPM (10% of 50 GPM is 5

GPM). A flow amount below 45 GPM would trigger the low flow

variance alarm.

10. Press the NEXT button to go to the Low Shutdown field. If you want the system to shut down when a low flow

is detected, press the + button to enter Y (yes).

11. When you have finished making changes, turn the dial to the Auto Run position.

Managing Concurrent Zones

In the BaseStation 3200, you manage the number of zones that can run concurrently at the following levels:

Mainline Flow Level – When you set up the design flow for the mainline and then set the Limit by Flow field to

Y (yes), the system uses the mainline design flow to determine how many zones can run concurrently. Refer to

Mainline Setup overview on page 59.

Controller and Program Level – If you want the controller to water more than one zone at a time, you must

configure the Zone Concurrency settings at the controller and program level.

Page

61

Advertising