Programming – Carlo Gavazzi WM4-96 User Manual

Page 26

Advertising
background image

VT-PT ratio

This function allows the
user to select the multiplier
value of the VT. Example: if

the primary of the VT (voltage
transformer) being connected is
20kV and the secondary is 100V,
the VT ratio will be 200 (given by
20000/100). If there is no VT, the
ratio will be “1.0”.

CT ratio

This function allows you to
select the value of the CT
ratio. Example: if the pri-

mary of the CT (current trans-
former) being connected is 300A
and the secondary is 5A, the CT
ratio corresponds to 60 (obtained
from the calculation: 300/5).
Choose the function CT RATIO by

means of the

and

keys;

press

to confirm then select

the desired value by means of the

and

keys and confirm

with

. To reset your choice and

go back to the main menu, press

.

F

S

S

26

Programming

Min/Max values

21

Digital inputs prog.

17

28

33

If the CT ratio is modified, then all the MIN/MAX val-
ues and the partial energy meters are reset.