Technical features

Load profile

73

Additional errors

72

79

83

Output specifications

RS422/RS485 (on request)

Bidirectional multidrop (static and dynamic variables)

Connections: 2 or 4 wires, max. distance 1200m, termina-

tion directly on the module.

Addresses: from 1 to 255, key-pad programmable.

Protocol: RTU MODBUS/JBUS.

Data (bidirectional) dynamics (reading only): all displayable

variables.

Statics (reading only): all the configuration parameters, ener-

gy reset, activation of digital outputs.

Data format: 1 start-bit, 8 data-bit, no parity/even

parity/odd parity, 1 stop bit.

Baud rate: 1200, 2400, 4800 and 9600bit/s selectable.

Insulation: by means of optocouplers, 4000 V

RMS

between

output and measuring input, 4000 V

RMS

between output and

power supply input.

RS232 (on request)

Bidirectional (static and dynamic variables)

Connections: 3 wires, max. distance 15m.

Data format: 1 start bit, 8 data bit, no parity, 1 bit stop.

Baud rate: 2400, 4800, 9600, 38400 bit/s.

Protocol: MODBUS RTU (JBUS).

Other features: as per RS422/485.

Communication by means of modem

Analogue modem for the remote communication of all the

data measured and managed by WM4.

Recommended external communication modem: US

Robotics.