Useful info – Carlo Gavazzi WM4-96 User Manual

Page 57

Advertising
background image

57

Useful Info

Dimensions, Panel cut-out

55

Language

56

61

59

higher value of this coefficient results in a higher settling time,
that means a higher stability. The best result is generally obtained
by setting the filtering coefficient at a value equal to at least 10
times the value of the range parameter. Considering the example
above: 1.5*10=15. To enhance the stability, you may also
increase the filtering coefficient (values within 1 and 255 only).

What is ASY

The ASY variable allows you to control the symmetry of the
star / delta voltages (for systems without neutrals) and star
voltages (for systems with neutral). The variable is calculat-
ed as follows:

where the first formula is to be applied with delta systems,
while the minimum value calculated between the two is to
be used for the star systems.

It’s very important, as a general rule, to plug in and
extract the optional modules only when the instru-
ment is switched off.

L

IST OF THE DISPLAYED VARIABLE PAGES

No

1

ST

variable

2

ND

variable 3

RD

variable 4

TH

variable

0

Selectable

Selectable Selectable

Selectable

1

V L1

V L2

V L3

V L-N

Σ

2

V L1-2

V L2-3

V L3-1

V L

Σ

3

A L1

A L2

A L3

A

Σ

4

W L1

W L2

W L3

W

Σ

Advertising