Outputs / other settings – Carlo Gavazzi WM4-96 User Manual

Page 46

Advertising
background image

46

Outputs / Other settings

Diagnostic

41

Installed power

44

48

55

The meaning of the symbols on the display is the following:
OUT C0 (1): digital output SLOT C0, channel 1

OUT C1 (2): digital output SLOT C1, channel 2
OUT D0 (3): digital output SLOT D0, channel 3
OUT D1 (4): digital output SLOT D1, channel 4

Pulse output

This function allows the user

to set the parameters of the
pulse output. The output can be
connected to a specific energy
and this energy can be connect-
ed to the desired tariff. The
measured energy is re-transmit-
ted by means of the pulse output
(the pulses/energy ratio of which

is programmable). Use

and

to select PULSE from the list

of available outputs; then con-

firm with

and choose from

the submenu ENERGY TYPE the
energy to be retransmitted using

and

: consumed active

energy (kWh +), generated active
energy (kWh -), consumed reac-
tive energy (kvarh +), generated

S

F

F

F

F

S

S

S

S

S

S

1.2..
..2.1

reactive energy (kvarh -), press the

key to open the

menu of energy/pulse output management. There are five
possible selections: TOTAL, output connected to the total
energy meter; TARIFF, output connected to the desired tariff