Crestron Commercial Lighting Design Guide

30

G

reen Light

Expr

ess

GLPX Panels

Crestron GLPX panels are configurable for dimming or switching and come
equipped with Green Light Express modules.

When specifying and ordering a GLPX panel, construct a model name as
shown to the right. Possible choices are listed underneath each blue box.
The numbered steps below describe each choice in detail.

Examples: GLPX-HSW-16
GLPX-HDSW-56



1. Module Type

GLPX-___-

Use the table to determine the type of dimming or switching module required.

___

Modules

SW

HSW

HDSW

FLV

2DIM8

Module Types

High-inrush

Switching

Arcless High-

inrush Switching

Heavy Duty

Switching

0-10V Dimming

Dimming

Voltages

120/230/277

120/230/277

120/230/277

120/230/277

120/230/277

Lighting Output
Capacity

16A

16A

20A

16A

16A

Motor Output Capacity
(120/230/277 V)

1/2/2 hp

0.5/1/1 hp

0.5/1.5/1.5 hp

0.5/1.5/1.5

0.5/1/1 hp

Rated Relay Lifetime

Up to 100,000

1,000,000

30,000

1,000,000

1,000,000

Additional Info

Page 31

Page 26

Page 32

Page 27

Page 34










2. Number of Loads

GLPX-___-

Find the row in the table that matches your choice in step 1. In that row is the maximum number of loads for each cabinet size.

___

Cabinet Size

Small

Medium

Large

M

a

ximum # of

L

o

ads

SW

8

24

56

HSW

8

16

32

HDSW

8

24

56

FLV

-

8

16

2DIM8

8

16

32

Height

12 5/16 in (31.24 cm)

24 1/4 in (61.60 cm)

39 21/32 in (100.71 cm)

Width

14 1/8 in (35.89 cm)

16 1/8 in (40.89 cm)

16 1/8 in (40.89 cm)

Depth

4 3/8 in (11.08 cm)

4 7/16 in (11.23 cm)

4 7/16 in (11.23 cm)

Note: If using 3-wire fluorescent dimming with the 2DIM8, the actual number of loads will be half the specified amount. For
example, a panel specified for 16 2DIM8 loads can control up to eight 3-wire ballasts.

What is Arcless Switching?

Crestron offers two switching relay types: high-inrush and arcless high-inrush. Arcless high-inrush relays use a TRIAC to handle the
current turn on. Within milliseconds, the continuous load is transferred from the TRIAC to a robust 50A mechanically-latching relay.
All switching occurs at the zero-cross point of the AC waveform under microprocessor control. This is a complete solution
eliminating arcing at the physical relay contacts during turn on and turn off. By eliminating arcing, the relay lifetime is increased
substantially.

GLPX

Module

Type

Number of

Loads

-

-

1
2
3

...

54
55
56

SW

HSW

HDSW

FLV

2DIM8

GLPX Model Naming System