Step 8 — Adjust Factory-Installed Options

APOLLO CONTROL — The optional Apollo control is used
to actively monitor all modes of operation as well as indoor
(evaporator) fan status, filter status, and indoor-air quality. The
Apollo control is designed to work with Carrier TEMP and
VVT

®

systems.

The thermostat must be wired to the Apollo control before

starting the unit. Refer to the Apollo control installation
instructions for information on installing the thermostat. See
Fig. 12 for Apollo location.
MANUAL OUTDOOR-AIR DAMPER — The outdoor-air
hood and screen are attached to the basepan at the bottom of
the unit for shipping.
Assembly:

1. Determine quantity of ventilation required for building.

Record amount for use in Step 8.

2. Remove and save evaporator coil access panel and

screws. See Fig. 13.

3. Separate hood and screen from basepan by removing the

screws and brackets securing them. Save all screws and
discard brackets.

4. Replace evaporator coil access panel using screws from

Step 2.

5. Place hood on front of evaporator coil access panel. See

Fig. 14 for hood details. Secure top of hood with the
screws removed in Step 3. See Fig. 15.

6. Remove and save 6 screws (3 on each side) from sides of

the manual outdoor-air damper. Remove and save 2 man-
ual outdoor-air adjustment screws (one on each side of
damper blade).

7. Align screw holes on hood with screw holes on side of

manual outdoor-air damper. See Fig. 14 and 15. Secure
hood with 6 side screws from Step 6.

8. Adjust minimum position setting of the damper blade by

adjusting the 2 manual outdoor-air adjustment screws on
the front of the damper blade. See Fig. 13. Slide blade
vertically until it is in the appropriate position determined
by Fig. 16. Tighten screws.

9. Remove and save screws currently on sides of hood.

Insert screens. Secure screens to hood using the screws.
See Fig. 15.

WIRING TO
THERMOSTAT

APOLLO
CONTROL

CONTROL
WIRING

Fig. 12 — Apollo Control Factory-Installed

in Typical Unit

Fig. 13 — Damper Panel with Manual

Outdoor-Air Damper Installed

Fig. 14 — Outdoor-Air Hood Details

Fig. 15 — Damper with Hood Attached

Advertising
This manual is related to the following products: