Table 16 — Fan Performance, 48TF012 — Horizontal Discharge Units (SI)

LEGEND

NOTES:

1. Boldface indicates field-supplied drive required. (See Note 5.)

2.

indicates field-supplied motor and drive are required.

3. Values include losses for filters, unit casing, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact

your Carrier representative to verify.

5. Standard drive range is 9.5 to 13.0 r/s. All other speeds require

a field-supplied drive.

6. Maximum continuous BkW is 1.79. Extensive motor and electri-

cal testing on these units ensures that the full range of the
motor can be utilized with confidence. Using the fan motors up
to the ratings shown will not result in nuisance tripping or pre-
mature motor failure. Unit warranty will not be affected.

7. Interpolation is permissible. Do not extrapolate.

AIRFLOW

(L/s)

EXTERNAL STATIC PRESSURE (Pa)

50

100

150

200

250

R/s

BkW

R/s

BkW

R/s

BkW

R/s

BkW

R/s

BkW

1500

9.1

0.49

10.5

0.63

11.6

0.77

12.6

0.89

13.5

0.99

1550

9.4

0.54

10.7

0.68

11.8

0.82

12.8

0.96

13.7

1.06

1600

9.6

0.59

10.9

0.73

12.0

0.88

13.0

1.02

13.9

1.14

1650

9.8

0.65

11.1

0.80

12.2

0.95

13.2

1.09

14.1

1.22

1700

10.1

0.71

11.3

0.86

12.4

1.01

13.4

1.16

14.2

3.10

1750

10.3

0.77

11.5

0.92

12.6

1.07

13.5

1.23

14.4

1.38

1800

10.6

0.84

11.7

0.98

12.8

1.14

13.7

1.30

14.6

1.47

1850

10.8

0.92

11.9

1.04

13.0

1.21

13.9

1.39

14.8

1.55

1900

11.1

1.00

12.1

1.14

13.2

1.29

14.1

1.47

15.0

1.64

1950

11.3

1.09

12.3

1.22

13.4

1.38

14.3

1.55

15.2

1.72

2000

11.6

1.18

12.6

1.31

13.6

1.47

14.5

1.65

15.3

1.82

2050

11.9

1.28

12.8

1.40

13.8

1.56

14.7

1.73

15.5

1.92

2100

12.1

1.38

13.0

1.50

14.0

1.64

14.9

1.82

15.8

2.02

2150

12.4

1.49

13.2

1.60

14.2

1.73

15.1

1.93

15.9

2.13

2200

12.7

1.61

13.4

1.70

14.4

1.83

15.3

2.04

16.1

2.24

2300

12.9

1.74

13.7

1.81

14.6

1.93

15.5

2.15

2350

13.2

1.86

13.9

1.93

14.8

2.03

15.7

2.27

2400

13.5

2.00

14.2

2.05

15.0

2.14

2500

14.4

2.14

15.2

2.25

AIRFLOW

(L/s)

EXTERNAL STATIC PRESSURE (Pa)

300

350

400

450

500

R/s

BkW

R/s

BkW

R/s

BkW

R/s

BkW

R/s

BkW

1500

14.5

1.13

15.2

1.22

16.1

1.40

16.8

1.54

17.7

1.82

1550

14.6

1.20

15.4

1.30

16.2

1.43

16.9

1.60

17.8

1.86

1600

14.8

1.26

15.6

1.40

16.3

1.50

17.1

1.68

17.9

1.91

1650

14.9

1.33

15.7

1.48

16.5

1.60

17.2

1.72

18.0

1.97

1700

15.0

1.42

15.9

1.56

16.7

1.70

17.3

1.81

18.0

1.97

1750

15.2

1.51

16.0

1.64

16.8

1.79

17.5

1.91

18.2

2.04

1800

15.4

1.61

16.2

1.73

17.0

1.89

17.7

2.03

18.3

2.15

1850

15.6

1.71

16.3

1.84

17.1

1.98

17.8

2.15

18.5

2.27

1900

15.8

1.80

16.5

1.94

17.2

2.07

18.0

2.24

18.7

2.40

1950

16.0

1.91

16.7

2.06

17.4

2.19

2000

16.2

2.01

16.9

2.17

17.6

2.31

2050

16.3

2.10

17.1

2.29

2100

16.5

2.21

2150

16.7

2.32

2200

16.9

2.43

2300

2350

2400

2500

BkW — Fan Input kW x Motor Efficiency