5table 1a — physical data (si) – Carrier 48TFE008-014 User Manual

Page 5

Advertising
background image

5

Table 1A — Physical Data (SI)

LEGEND

*Weight of 356 mm (14-in.) roof curb.

NOTE: The 48TF units have a loss-of-charge (low pressure) switch located in
the liquid line.

UNIT SIZE 48TF

008

012

014

Low Heat (D), Medium Heat (E), High Heat (F)

D

E

F

D

E

F

D

E

NOMINAL CAPACITY (kW)

21.5

29.2

35.9

OPERATING WEIGHT (kg)

Unit

395

469

476

Durablade Economizer

20

20

20

EconoMi$er

28

28

28

Roof Curb*

65

65

65

COMPRESSOR TYPE

Hermetic

Hermetic

Scroll

Quantity

2

2

2

Oil (ml)

1479 ea

1479 ea

1597 ea

REFRIGERANT TYPE

R-22

Operating Charge (kg)

Circuit 1

2.10

3.08

3.49

Circuit 2

2.22

3.22

3.49

CONDENSER COIL

Enhanced Copper Tubes, Aluminum Lanced Fins

Rows...Fins/m

1...669

2...669

2...669

Total Face Area (sq m)

1.90

1.92

2.30

CONDENSER FAN

Propeller Type

Nominal L/s

2880

3050

3050

Quantity...Diameter (mm)

2...559

2...559

2...559

Motor BkW...r/s

.19...15.5

.19...15.5

.19...15.5

EVAPORATOR COIL

Enhanced Copper Tubes, Aluminum Double-Wavy Fins, Acutrol™ Feed Device

Rows...Fins/m

3...590

3...590

4...590

Total Face Area (sq m)

0.74

0.93

1.03

EVAPORATOR FAN

Centrifugal Type

Quantity...Size (mm x mm)

1...381 x 381

1...381 x 381

1...381 x 381

Type Drive

Belt

Belt

Belt

Nominal L/s

1230

1700

1980

Motor kW

1.12

1.50

2.24

Maximum Continuous BkW

1.79

1.79

2.76

Motor Frame Size

56

56

56

Fan r/s Range

8.2-11.7

9.5-13.0

12.0-15.0

Motor Bearing Type

Ball

Ball

Ball

Maximum Allowable r/s

26.7

26.7

26.7

Motor Pulley Pitch Diameter Min/Max (mm)

61/86

71/97

102/127

Nominal Motor Shaft Diameter (mm)

16

16

22

Fan Pulley Pitch Diameter (mm)

178

178

203

Nominal Fan Shaft Diameter (mm)

25

25

25

Belt, Quantity...Type...Length (mm)

1...A...1245

1...A...1245

1...A...1346

Pulley Center Line Distance (mm)

425-489

403-445

403-445

Speed Change per Full Turn of

Movable Pulley Flange (r/s)

.70

.70

.60

Movable Pulley Maximum Full Turns

From Closed Position

5

5

5

Factory Setting

5

5

5

Factory Speed Setting (r/s)

8.2

9.5

12.0

Fan Shaft Diameter at Pulley (mm)

25

25

25

FURNACE SECTION

Rollout Switch Cutout Temp (C)

90.6

90.6

90.6

Burner Orifice Diameter (mm)

Natural Gas

— Std

3.05

3.05

3.05

3.28

3.05

3.28

Liquid Propane — Alt

2.44

2.44

2.44

2.59

2.44

2.59

Thermostat Heat Anticipator Setting (amps)
400 v

Stage 1

.14

.14

.14

.14

.14

Stage 2

.14

.20

.20

.20

.20

Gas Input (kW)

Stage 1

21.1

31.9

39.8

31.9

39.8

43.9

39.8

43.9

Stage 2

31.4

50.4

59.8

50.4

59.8

65.6

59.8

65.6

Efficiency (Steady State) (%)

80

80

80

Temperature Rise Range (C)

–6-10

2-18

7-24

2-18

7-24

4-21

7-24

4-21

Manifold Pressure (kPa)

Natural Gas

— Std

8.3

8.3

8.3

Liquid Propane — Alt

8.3

8.3

8.3

Field Gas Connection Size (mm)

13

19

19

19

19

19

19

19

HIGH-PRESSURE SWITCH (kPa)

Standard Compressor

Internal Relief (Differential)

3103 ± 345

3448 ± 345

Cutout

2951

Reset (Auto.)

2206

LOW-PRESSURE SWITCH (kPa)

Cutout

48 ± 21

Reset (Auto.)

152 ± 48

FREEZE PROTECTION THERMOSTAT

Opens (C)

–1 ± 3

Closes (C)

7 ± 3

OUTDOOR-AIR INLET SCREENS

Cleanable

Quantity...Size (mm)

1...508 x 635 x 25
1...406 x 635 x 25

RETURN-AIR FILTERS

Throwaway

Quantity...Size (mm)

4...406 x 508 x 51

4...508 x 508 x 51

4...508 x 508 x 51

Bhp —

Brake Horsepower

BkW —

Fan Input Watts x Motor Efficiency

Advertising
This manual is related to the following products: