Carrier 48TFE008-014 User Manual

Page 4

Advertising
background image

4

Although unit is weatherproof, guard against water from

higher level runoff and overhangs.

Position unit on roof curb so that the following clearances

are maintained: 7 mm (

1

/

4

-in.) clearance between roof curb and

base rails on each side and duct end of unit; 84 mm (3

5

/

16

-in.)

clearance between roof curb and condenser coil end of unit.
(See Fig. 2, section C-C.)

Locate mechanical draft system flue assembly at least

1219 mm (48 in.) from any opening through which combustion
products could enter the building, and at least 1219 mm (48 in.)
from an adjacent building or combustible material. When unit
is located adjacent to public walkways, flue assembly must be
at least 2.13 m (7 ft) above grade.

Flue vent discharge must have a minimum horizontal clear-

ance of 1219 mm (48 in.) from electric and gas meters, gas reg-
ulators, and gas relief equipment.

Flue gas can deteriorate building materials. Orient unit so

that flue gas will not affect building materials.

Adequate combustion-air space must be provided for proper

operation of this equipment. Be sure that installation complies
with all local codes and Section 5.3, Air for Combustion and
Ventilation, NFGC (National Fuel Gas Code), ANSI (Ameri-
can National Standards Institute), latest revision, U.S.A.
Standards.

(Copy continued on page 8.)

DRAIN PLUG

MAXIMUM ALLOWABLE

DIFFERENCE mm (in.)

A-B

B-C

A-C

13 (0.5)

25 (1.0)

25 (1.0)

Fig. 3 — Unit Leveling Tolerances

NOTE: Drain plug is shown in factory-installed position.

Fig. 4 — Condensate Drain Pan

NOTES:

1. Dimension in ( ) is in millimeters.
2. Hook rigging shackles through holes in base rail as shown in

detail ‘‘A.’’ Holes in base rails are centered around the unit cen-
ter of gravity. Use wooden top skid when rigging to prevent rig-
ging straps from damaging unit.

3. Weights include base unit without economizer. See Tables 1A

and 1B for economizer weights.

All panels must be in place when rigging.

Fig. 5 — Rigging Details

UNIT
48TF

MAX

WEIGHT

DIMENSIONS

‘‘A’’

‘‘B’’

‘‘C’’

lb

kg

in.

mm

in.

mm

in.

mm

D/E/F008

870 395 87.38 2219 40.25 1022 41.31 1050

D/E/F012

1035 469 87.38 2219 40.25 1022 49.31 1253

D/E014

1050 476 87.38 2219 40.25 1022 49.31 1253