Table 17 — Fan Performance, 48TF014 — Horizontal Discharge Units (SI)

LEGEND

NOTES:

1. Boldface indicates field-supplied drive required. (See Note 5.)
2.

indicates field-supplied motor and drive are required.

3. Values include losses for filters, unit casing, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact

your Carrier representative to verify.

5. Standard drive range is 12.0 to 15.0 r/s. All other speeds

require a field-supplied drive.

6. Maximum continuous BkW is 2.76. Extensive motor and electri-

cal testing on these units ensures that the full range of the
motor can be utilized with confidence. Using the fan motors up
to the ratings shown will not result in nuisance tripping or pre-
mature motor failure. Unit warranty will not be affected.

7. Interpolation is permissible. Do not extrapolate.

AIRFLOW

(L/s)

EXTERNAL STATIC PRESSURE (Pa)

50

100

150

200

225

R/s

BkW

R/s

BkW

R/s

BkW

R/s

BkW

R/s

BkW

1900

11.5

0.96

12.7

1.14

13.7

1.32

14.7

1.49

15.6

1.71

1950

11.8

1.04

12.9

1.22

13.9

1.40

14.9

1.57

15.8

1.80

2000

12.1

1.12

13.2

1.29

14.2

1.49

15.1

1.65

16.0

1.89

2050

12.3

1.18

13.4

1.38

14.4

1.59

15.3

1.75

16.2

1.96

2100

12.6

1.27

13.6

1.46

14.6

1.68

15.5

1.86

16.4

2.05

2150

12.8

1.36

13.9

1.56

14.9

1.78

15.7

1.96

16.6

2.15

2200

13.1

1.44

14.1

1.66

15.1

1.88

16.0

2.07

16.8

2.26

2250

13.3

1.53

14.4

1.75

15.3

1.99

16.2

2.20

17.0

2.36

2325

13.6

1.63

14.6

1.87

15.5

2.10

16.4

2.30

17.2

2.50

2400

13.9

1.74

14.9

1.98

15.8

2.20

16.6

2.44

17.4

2.64

2450

14.1

1.84

15.1

2.10

16.0

2.31

16.8

2.56

17.6

2.77

2500

14.4

1.95

15.4

2.22

16.2

2.44

17.1

2.69

17.8

2.90

2550

14.7

2.07

15.6

2.34

16.5

2.56

17.3

2.83

18.1

3.05

2600

14.9

2.18

15.8

2.47

16.7

2.69

17.5

2.96

18.3

3.20

2650

15.2

2.32

16.1

2.60

16.9

2.83

17.8

3.11

18.5

3.34

2700

15.4

2.44

16.4

2.74

17.2

2.96

18.0

3.26

18.7

3.51

2750

15.7

2.57

16.6

2.89

17.4

3.11

18.2

8.38

19.0

3.67

2800

15.9

2.71

16.9

3.03

17.7

3.27

18.4

3.55

19.2

3.84

2850

16.2

2.86

17.1

3.18

17.9

3.46

18.7

3.70

2900

16.5

2.98

17.3

3.32

18.2

3.57

18.9

3.85

2950

16.7

3.11

17.6

3.46

18.4

3.72

3000

17.0

3.25

17.8

3.60

18.7

3.87

3050

17.3

3.38

18.1

3.74

3100

17.5

3.52

18.3

3.89

AIRFLOW

(L/s)

EXTERNAL STATIC PRESSURE (Pa)

300

350

400

450

500

R/s

BkW

R/s

BkW

R/s

BkW

R/s

BkW

R/s

BkW

1900

16.6

1.91

17.5

2.11

18.2

2.29

18.9

2.44

19.3

2.55

1950

16.7

2.00

17.6

2.21

18.4

2.41

19.1

2.58

19.6

2.71

2000

16.9

2.11

17.8

2.31

18.6

2.52

19.3

2.71

19.9

2.87

2050

17.1

2.20

17.9

2.42

18.7

2.64

19.5

2.84

20.1

3.02

2100

17.2

2.30

18.1

2.53

18.9

2.76

19.6

2.97

20.3

3.17

2150

17.4

2.42

18.2

2.64

19.0

2.88

19.8

3.10

20.5

3.31

2200

17.6

2.52

18.4

2.76

19.2

2.99

20.0

3.23

20.7

3.45

2250

17.8

2.61

18.6

2.88

19.4

3.11

20.1

3.37

20.9

3.60

2235

18.0

2.71

18.8

3.00

19.5

3.26

20.3

3.49

21.0

3.75

2400

18.2

2.83

18.9

3.13

19.7

3.39

20.5

3.64

21.2

3.89

2450

18.4

2.97

19.1

3.24

19.9

3.52

20.6

3.77

2500

18.6

3.09

19.3

3.35

20.0

3.66

20.8

3.93

2550

18.8

3.25

19.5

3.49

20.2

3.81

2600

19.0

3.42

19.7

3.63

20.4

3.95

2650

19.2

3.58

19.9

3.81

2700

19.4

3.73

20.1

3.92

2750

19.7

3.91

2800

2850

2900

2950

3000

3050

3100

BkW — Fan Input kW x Motor Efficiency
R/s

Revolutions Per Second of Blower Wheel

Advertising
This manual is related to the following products: