Table 14 — Fan Performance, 48TF014 — Vertical Discharge Units (SI)

LEGEND

NOTES:

1. Boldface indicates field-supplied drive required. (See Note 5.)
2.

indicates field-supplied motor and drive are required.

3. Values include losses for filters, unit casing, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact

your Carrier representative to verify.

5. Standard drive range is 12.0 to 15.0 r/s. All other speeds

require a field-supplied drive.

6. Maximum continuous BkW is 2.76. Extensive motor and electri-

cal testing on these units ensures that the full range of the
motor can be utilized with confidence. Using the fan motors up
to the ratings shown will not result in nuisance tripping or pre-
mature motor failure. Unit warranty will not be affected.

7. Interpolation is permissible. Do not extrapolate.

AIRFLOW

(L/s)

EXTERNAL STATIC PRESSURE (Pa)

50

100

150

200

250

R/s

BkW

R/s

BkW

R/s

BkW

R/s

BkW

R/s

BkW

1900

12.5

1.10

13.5

1.27

14.4

1.42

15.3

1.63

16.1

1.81

1950

12.7

1.18

13.7

1.36

14.6

1.52

15.5

1.73

16.4

1.92

2000

13.0

1.27

14.0

1.46

14.9

1.62

15.7

1.81

16.6

2.02

2050

13.3

1.36

14.3

1.56

15.1

1.72

16.0

1.91

16.8

2.14

2100

13.6

1.46

14.5

1.66

15.4

1.84

16.2

2.01

17.0

2.25

2150

13.9

1.56

14.8

1.78

15.7

1.95

16.5

2.13

17.3

2.37

2250

14.2

1.67

15.1

1.89

15.9

2.07

16.7

2.24

17.5

2.48

2300

14.5

1.78

15.4

2.00

16.2

2.19

17.0

2.37

17.7

2.60

2350

14.8

1.89

15.7

2.13

16.4

2.32

17.2

2.51

18.0

2.72

2400

15.0

2.01

15.9

2.25

16.7

2.46

17.5

2.64

18.2

2.85

2450

15.4

2.16

16.2

2.38

17.0

2.60

17.7

2.79

18.5

2.99

2500

15.7

2.28

16.5

2.52

17.3

2.75

18.0

2.95

18.7

3.13

2550

15.9

2.43

16.8

2.65

17.5

2.90

18.2

3.10

18.0

3.29

2600

16.2

2.58

17.1

2.81

17.8

3.05

18.5

3.26

19.2

3.47

2650

16.5

2.72

17.3

2.95

18.1

3.22

18.8

3.43

19.4

3.64

2700

16.8

2.89

17.6

3.12

18.4

3.39

19.0

3.60

19.7

3.83

2750

17.1

3.05

17.9

3.28

18.7

3.56

19.3

3.80

20.0

4.01

2800

17.4

3.21

18.2

3.45

18.9

3.74

19.6

3.98

20.2

4.19

2850

17.7

3.40

18.5

3.64

19.2

3.93

19.9

4.18

20.5

4.41

2900

18.0

3.57

18.8

3.81

19.5

4.11

20.2

4.37

2950

18.3

3.76

19.1

4.02

19.8

4.29

3000

18.6

3.96

19.4

4.21

20.1

4.51

3050

18.9

4.15

19.6

4.40

3100

19.2

4.38

AIRFLOW

(L/s)

EXTERNAL STATIC PRESSURE (Pa)

300

350

400

450

500

R/s

BkW

R/s

BkW

R/s

BkW

R/s

BkW

R/s

BkW

1900

17.0

2.00

17.9

2.21

18.7

2.39

19.4

2.58

20.1

2.74

1950

17.2

2.11

18.0

2.31

18.8

2.51

19.6

2.71

20.3

2.88

2000

17.4

2.22

18.2

2.43

19.0

2.63

19.8

2.84

20.5

3.02

2050

17.6

2.33

18.4

2.54

19.2

2.76

19.9

2.97

20.7

3.17

2100

17.8

2.45

18.6

2.66

19.3

2.89

20.1

3.10

20.8

3.32

2150

18.0

2.59

18.8

2.79

19.5

3.01

20.3

3.24

21.0

3.46

2250

18.2

2.71

19.0

2.93

19.7

3.15

20.4

3.37

21.2

3.60

2300

18.5

2.85

19.2

3.05

19.9

3.29

20.6

3.52

21.3

3.76

2350

18.7

2.99

19.4

3.21

20.1

3.43

20.8

3.67

21.5

3.92

2400

18.9

3.12

19.6

3.36

20.3

3.59

21.0

3.82

21.7

4.08

2450

19.2

3.27

19.8

3.53

20.5

3.74

21.2

3.99

2500

19.4

3.38

20.1

3.67

20.7

3.93

21.4

4.15

2550

19.6

3.54

20.3

3.83

21.0

4.09

21.6

4.33

2600

19.9

3.69

20.5

4.01

21.2

4.27

2650

20.1

3.86

20.8

4.16

21.4

4.44

2700

20.4

4.03

21.0

4.32

2750

20.6

4.21

2800

20.9

4.40

2850

2900

2950

3000

3050

3100

BkW — Fan Input kW x Motor Efficiency