Carrier 48TFE008-014 User Manual

Page 32

Advertising
background image

32

Table 22 — Fan Performance, 48TF012 — Horizontal Discharge Units (English)

LEGEND

NOTES:

1. Boldface indicates field-supplied drive required. (See Note 5.)

2.

indicates field-supplied motor and drive are required.

3. Values include losses for filters, unit casing, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact

your Carrier representative to verify.

5. Standard drive range is 571 to 779 rpm. All other rpms require

a field-supplied drive.

6. Maximum continuous bhp is 2.4. Extensive motor and electrical

testing on these units ensures that the full range of the motor
can be utilized with confidence. Using the fan motors up to the
ratings shown will not result in nuisance tripping or premature
motor failure. Unit warranty will not be affected.

7. Interpolation is permissible. Do not extrapolate.

AIRFLOW

(Cfm)

EXTERNAL STATIC PRESSURE (in. wg)

0.2

0.4

0.6

0.8

1.0

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

3000

552

0.68

632

0.87

701

1.05

761

1.22

816

1.36

3100

565

0.74

644

0.93

711

1.12

772

1.31

825

1.45

3200

578

0.81

656

1.00

723

1.20

782

1.39

835

1.55

3300

591

0.88

668

1.08

734

1.28

793

1.47

845

1.65

3400

605

0.96

680

1.16

745

1.36

803

1.56

856

1.75

3500

619

1.04

691

1.23

755

1.44

813

1.65

867

1.86

3600

633

1.13

703

1.31

766

1.52

824

1.74

877

1.97

3700

648

1.23

714

1.39

777

1.61

835

1.85

887

2.07

3800

662

1.33

726

1.51

789

1.72

846

1.95

897

2.18

3900

677

1.44

738

1.61

801

1.82

857

2.06

908

2.29

4000

692

1.55

750

1.73

813

1.94

868

2.17

918

2.40

4100

707

1.67

762

1.84

825

2.05

878

2.28

929

2.53

4200

722

1.80

775

1.97

837

2.16

889

2.40

941

2.66

4300

737

1.94

787

2.09

848

2.27

900

252

952

2.80

4400

752

2.08

800

2.21

860

2.39

912

2.66

962

2.93

4500

768

2.24

814

2.35

871

2.51

924

2.80

973

3.07

4600

783

2.40

827

2.50

883

2.64

937

2.95

983

3.21

4700

799

2.56

841

2.64

894

2.77

949

3.10

994

3.36

4800

814

2.74

855

2.80

906

2.91

961

3.26

4900

868

2.90

918

3.05

972

3.40

5000

883

3.10

931

3.21

AIRFLOW

(Cfm)

EXTERNAL STATIC PRESSURE (in. wg)

1.2

1.4

1.6

1.8

2.0

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

3000

871

1.54

918

1.67

967

1.89

1010

2.09

1063

2.46

3100

879

1.63

928

1.78

973

1.94

1018

2.17

1070

2.51

3200

887

1.71

937

1.90

981

2.04

1026

2.26

1075

2.57

3300

895

1.80

946

2.00

991

2.16

1032

2.32

1080

2.64

3400

904

1.91

953

2.10

1000

2.29

1041

2.44

1083

2.65

3500

914

2.03

961

2.20

1009

2.41

1051

2.57

1090

2.74

3600

924

2.15

970

2.32

1017

2.53

1061

2.72

1099

2.88

3700

935

2.28

980

2.45

1024

2.64

1069

2.87

1109

3.03

3800

946

2.40

989

2.58

1033

2.76

1077

2.99

1118

3.20

3900

956

2.53

1000

2.73

1042

2.91

1085

3.12

1127

3.36

4000

967

2.66

1010

2.87

1052

3.06

1093

3.24

4100

977

2.78

1021

3.02

1062

3.22

1102

3.41

4200

987

2.91

1032

3.17

1072

3.38

4300

999

3.04

1042

3.32

4400

1008

3.19

4500

1019

3.34

4600

4700

4800

4900

5000

Bhp — Brake Horsepower at Motor Shaft
Rpm — Revolutions Per Minute of Blower Wheel

Advertising