Carrier 48TFE008-014 User Manual

Page 28

Advertising
background image

28

Table 18 — Fan Performance, 48TF008 — Vertical Discharge Units (English)

LEGEND

NOTES:

1. Boldface indicates field-supplied drive required. (See Note 5.)

2.

indicates field-supplied motor and drive are required.

3. Values include losses for filters, unit casing, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact

your Carrier representative to verify.

5. Standard drive range is 492 to 700 rpm. All other rpms require

a field-supplied drive.

6. Maximum continuous bhp is 2.4. Extensive motor and electrical

testing on these units ensures that the full range of the motor
can be utilized with confidence. Using the fan motors up to the
ratings shown will not result in nuisance tripping or premature
motor failure. Unit warranty will not be affected.

7. Interpolation is permissible. Do not extrapolate.

AIRFLOW

(Cfm)

EXTERNAL STATIC PRESSURE (in. wg)

0.2

0.4

0.6

0.8

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

2200

506

0.52

586

0.72

656

0.95

718

1.18

2250

514

0.55

593

0.76

662

0.99

724

1.22

2300

521

0.56

600

0.79

668

1.02

730

1.26

2400

536

0.63

613

0.85

680

1.09

741

1.34

2500

551

0.69

626

0.93

693

1.17

753

1.43

2550

559

0.72

634

0.97

700

1.21

759

1.48

2600

567

0.75

641

1.00

706

1.25

764

1.52

2700

582

0.83

655

1.08

719

1.34

776

1.61

2800

598

0.90

670

1.17

732

1.43

789

1.71

2900

614

0.98

684

1.25

745

1.53

802

1.81

3000

630

1.07

699

1.35

759

1.63

815

1.92

3100

646

1.16

714

1.45

773

1.74

828

2.04

3200

662

1.26

729

1.55

787

1.86

841

2.16

3300

679

1.36

744

1.66

801

1.98

854

2.29

3400

695

1.47

759

1.78

816

2.10

867

2.42

3500

712

1.59

774

1.90

830

2.23

881

2.56

3600

729

1.71

790

2.03

845

2.37

895

2.71

3700

745

1.84

805

2.17

860

2.52

909

2.87

3750

754

1.91

813

2.24

868

2.59

917

2.95

AIRFLOW

(Cfm)

EXTERNAL STATIC PRESSURE (in. wg)

1.0

1.2

1.4

1.6

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

2200

776

1.43

838

1.78

898

2.21

935

2.58

2250

781

1.78

841

1.81

902

2.25

939

2.60

2300

786

1.50

843

1.83

905

2.28

943

2.62

2400

796

1.59

849

1.88

910

2.31

952

2.74

2500

808

1.69

859

1.96

912

2.31

963

2.81

2550

814

1.74

864

2.01

915

2.34

968

2.81

2600

819

1.79

869

2.06

918

2.37

973

2.81

2700

831

1.89

880

2.17

927

2.47

976

2.84

2800

842

2.00

892

2.29

938

2.58

983

2.92

2900

854

2.11

903

2.42

949

2.71

993

3.03

3000

866

2.23

915

2.54

961

2.85

1003

3.17

3100

878

2.35

926

2.67

972

3.00

1015

3.32

3200

891

2.48

938

2.81

983

3.14

1026

3.47

3300

904

2.61

950

2.95

995

3.30

3400

917

2.75

963

3.10

1007

3.45

3500

930

2.90

976

3.25

3600

943

3.05

988

3.41

3700

956

3.22

3750

963

3.30

Bhp — Brake Horsepower at Motor Shaft
Rpm — Revolutions Per Minute of Blower Wheel

Advertising