Table 15 — Fan Performance, 48TF008 — Horizontal Discharge Units (SI)

LEGEND

NOTES:

1. Boldface indicates field-supplied drive required. (See Note 5.)

2.

indicates field-supplied motor and drive are required.

3. Values include losses for filters, unit casing, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact

your Carrier representative to verify.

5. Standard drive range is 8.2 to 11.7 r/s. All other speeds require

a field-supplied drive.

6. Maximum continuous BkW is 1.79. Extensive motor and electri-

cal testing on these units ensures that the full range of the
motor can be utilized with confidence. Using the fan motors up
to the ratings shown will not result in nuisance tripping or pre-
mature motor failure. Unit warranty will not be affected.

7. Interpolation is permissible. Do not extrapolate.

AIRFLOW

(L/s)

EXTERNAL STATIC PRESSURE (Pa)

50

100

150

200

225

R/s

BkW

R/s

BkW

R/s

BkW

R/s

BkW

R/s

BkW

1075

8.1

0.34

9.5

0.49

10.7

0.66

11.8

0.81

12.4

0.92

1125

8.4

0.39

9.7

0.53

10.9

0.71

12.0

0.89

12.5

0.98

1150

8.6

0.42

9.9

0.58

11.1

0.76

12.2

0.96

12.7

1.05

1200

8.9

0.46

10.2

0.64

11.3

0.81

12.4

1.02

12.8

1.11

1250

9.1

0.51

10.4

0.70

11.5

0.87

12.6

1.08

13.0

1.19

1300

9.4

0.56

10.7

0.75

11.7

0.93

12.7

1.14

13.2

1.25

1400

9.7

0.62

10.9

0.82

12.0

0.99

12.9

1.22

13.4

1.33

1450

10.0

0.67

11.2

0.88

12.2

1.07

13.2

1.27

13.6

1.40

1500

10.2

0.74

11.4

0.94

12.4

1.15

13.4

1.36

13.8

1.48

1550

10.5

0.80

11.7

1.02

12.7

1.23

13.6

1.44

14.0

1.56

1600

10.8

0.88

11.9

1.09

12.9

1.32

13.8

1.53

14.2

1.65

1650

11.1

0.97

12.2

1.17

13.2

1.41

14.0

1.63

14.4

1.75

1700

11.4

1.04

12.4

1.25

13.4

1.51

14.3

1.73

14.7

1.85

1750

11.7

1.12

12.7

1.35

13.7

1.61

14.5

1.85

14.9

1.97

1800

12.0

1.23

13.0

1.45

13.9

1.70

14.8

1.95

15.1

2.07

1850

12.2

1.33

13.2

1.54

14.2

1.81

15.0

2.08

15.4

2.20

1900

12.5

1.42

13.5

1.65

14.4

1.92

15.2

2.20

15.6

2.34

AIRFLOW

(L/s)

EXTERNAL STATIC PRESSURE (Pa)

250

300

350

400

R/s

BkW

R/s

BkW

R/s

BkW

R/s

BkW

1075

12.9

1.03

13.9

1.29

15.0

1.60

15.7

1.89

1125

13.0

1.08

14.0

1.34

15.1

1.68

15.9

1.92

1150

13.1

1.13

14.1

1.38

15.2

1.69

16.0

1.96

1200

13.3

1.21

14.3

1.42

15.2

1.74

16.0

2.01

1250

13.5

1.29

14.4

1.48

15.3

1.78

16.2

2.06

1300

13.7

1.37

14.5

1.56

15.4

1.81

16.3

2.09

1400

13.9

1.44

14.7

1.66

15.5

1.84

16.4

2.19

1450

14.1

1.52

14.9

1.77

15.7

1.97

16.5

2.18

1500

14.3

1.60

15.1

1.86

15.9

2.08

16.6

2.29

1550

14.2

1.68

15.3

1.94

16.1

2.21

16.8

2.43

1600

14.8

1.77

15.5

2.04

16.3

2.31

17.0

2.55

1650

14.9

1.86

15.7

2.13

16.5

2.42

17.2

2.70

1700

15.1

1.97

15.9

2.24

16.6

2.52

17.4

2.82

1750

15.3

2.08

16.1

2.35

16.3

2.64

17.6

2.94

1800

15.5

2.20

16.3

2.45

17.0

2.76

17.7

3.05

1850

15.8

2.32

16.5

2.58

17.2

2.87

17.9

3.19

1900

16.0

2.46

16.7

2.70

17.5

2.99

18.1

3.31

BkW — Fan Input kW x Motor Efficiency
R/s

Revolutions Per Second of Blower Wheel

Advertising
This manual is related to the following products: