16 EtherNet/IP Installation and Programming Manual

4.2.2

Status Data

Indicator status data is returned in the second word (see Table 4-4). Batch commands
return batch status in place of the low byte (see Table 4-5). Setpoint commands return
batch status in the low byte of the status word and the setpoint number in the high
byte.

Bit-0 Errors

• PLC command failed to execute.
• No configuration has taken place.
• Scale parameter is out of range.
• Print error has occurred.
• Load error has occurred.
• Memory error has occurred.
• Analog to digital converter error.
• Tare error.
• Scale over range error.
• Scale under range error.
• Non-recoverable configuration store error.
• Indicator in configuration mode.

Word 2

Bit

Indicator Status Data

Value=0

Value=1

00

Error **

(see See “Bit-0 Errors” on

page 16.)

No error

01

Tare not entered

Tare entered

02

Not center of zero

Center of zero

03

Weight invalid

Weight OK

04

Standstill

In motion

05

Primary units

Other units

06

Tare not acquired

Tare acquired

07

Gross weight

Net weight

08

Channel number

Least significant bit first.

09

10

11

12

13

Not used

14

Integer data

Floating point data

15

Positive weight

Negative weight

** This error condition does not necessarily mean the weight

being reported is invalid. Refer to the “Weight invalid” bit.

Table 4-4. Indicator Status Data Format