Commands 17

4.2.3

Value

Weight data is returned to the master in the third and fourth words of the input
command format, depending on the command and the value type. The weight data
returned is the displayed weight after the command is executed, unless the command
specifies otherwise.

4.2.4

Setting a Float Value:

Setting a float value in a setpoint requires the value to be sent in two separate integer
values. Most PLCs have a mechanism to take a float value and separate it into to
integer values.
The following is what is needed in the output words to set the value of Setpoint #1 to
10000.

Command word = 304
Parameter word = 1
MSW = 17948
LSW = 16384

4.2.5

Reading a Float Value:

When a float value is read it will be retuned in two integers that will represent the
float value.
The PLC will need to combine MSW and LSW integer values back into a float value.
The following is what is will be returned in the input words if the weight on the scale
is 800.5.

Command Word = 288
Status word = Scale status
MSW= 17480
LSW = 8192

Word 2

Bit

Batch Function Status Data

Value=0

Value=1

00

Digital input 4 OFF

Digital input 4 ON

01

Digital input 3 OFF

Digital input 3 ON

02

Digital input 2 OFF

Digital input 2 ON

03

Digital input 1 OFF

Digital input 1 ON

04

Batch not paused

Batch paused

05

Batch not running

Batch running

06

Batch not stopped

Batch stopped

07

Alarm OFF

Alarm ON

08

Setpoint number

09

10

11

12

13

Not used

14

Integer data

Floating point data

15

Positive weight

Negative weight

Table 4-5. Batch Function Status Data Format