8 fldbus menu, 9 vers menu, Fldbus menu – Rice Lake 920i Installation Manual V3.07 User Manual

Page 55: Vers menu, S e c t i o n 3 . 2 . 8 o n p a g e 4 9, Scale is configured, a, Softkey also provides access to, Diagnostic information

Advertising
background image

Configuration

49

3.2.8

FLDBUS Menu

The FLDBUS menu is shown only if a DeviceNet, Profibus, EtherNet/IP, or ControlNet option card is installed.
The SWAP parameter on the FLDBUS menu enables byte swapping by the

iRite

BusCommand handler rather

than requiring a SWP (SWAPBYTE) instruction in the PLC. Byte swapping is enabled by default for DeviceNet
cards; for all other fieldbus cards, byte swapping is disabled by default.

The DATASIZE parameter sets the size of the BusCommand handler data transfers. The default value (8 bytes, or
4 words) matches the default data size specified in the EDS and GSD files, and used by the standard discrete
transfer commands. DATASIZE can be set to any value from 2–128 bytes (1–64 words), but the value specified
must match the data size set for the PLC Scanner I/O data size.

Figure 3-18. FLDBUS Menu

3.2.9

VERS Menu

The VERS menu can be used to check the installed software version or, by using the

Reset Config

softkey, to

restore all configuration parameters to their factory default values. There are no parameters associated with the
Version menu: when selected, the indicator displays the installed software version number.

Figure 3-19. Version Menu

The

Contacts

softkey on the Version menu allows display of contact information (see “FEATURE Menu,

CONTACT Submenu” on page 42). If an

iQUBE

scale is configured, a

Diagnostics

softkey also provides access to

iQUBE

diagnostic information.

FLDBUS Menu

Parameter

Choices

Description

Level 2 submenus

SWAP

YES
NO

Specifies whether byte-swapping is enabled. For DeviceNet cards, this parameter defaults to YES;
for all other cards the default value is NO.

DATASIZE

8
2-128

Specifies the data size, in bytes, that the BusCommand handler transfers. If this parameter is set to
a value other than the default (8 bytes), ensure that it matches the Scanner I/O data size specified
for the PLC.

SCALES

SERIAL

FEATURE

PFORMT

SETPTS

DIG I/O

FLDBUS

VERS

SWAP

YES

NO

DATASIZE

8

data_size

If SWAP = YES

SCALES

SERIAL

FEATURE

PFORMT

SETPTS

DIG I/O

VERS

Software

version

Advertising