Set Thermidistat Control Configuration

Configuration options enable the installer to configure the Thermidistat Control

for a particular installation. Most are not presented to the homeowner and

therefore must be properly set by the installer. (Only those marked with an

asterisk * below are available to the homeowner.) The homeowner

configurations are described in the owner’s manual. A special procedure allows

entry into the configuration mode. Selections can be made while in configuration

mode. Description of each selection and how to use the configuration mode

follows.
CONFIGURATION OPTIONS − SUMMARY
Option 01 — Equipment Type
Option 02 — Clean Filter Timer Adjustment
Option 03* — Fahrenheit/Centigrade Selection
Option 04 — Fan (G) on with W/W1 Selection
Option 05 — Room Air Temperature Sensing (programmable

models only)

Option 06 — Cooling Lockout Below 55

_F/13_C Selection (only

available if outdoor air sensor is present)

Option 07 — Zoning
Option 08 — Auxiliary Heat Lockout Temperature Setting (only

available when heat pump is used and when

outdoor air temperature sensor is present)

Option 09 — Heat Pump Lockout Temperature Balance Point (only available

when outdoor air temperature sensor is present)

Option 10 — Reversing Valve