Carrier PERFORMANCETSERIES EDGER THERMIDISTATT CONTROL TP-PRH-A User Manual

Page 58

Advertising
background image

58

Programmable Fan (programmable models only)
The fan output can be programmed based on period of the day. When

programming for each day and period the fan can be set to On or AUTO. If the

fan button is pressed to change from On to Auto or vice versa when

programmable fan has been enabled, the manual change will only remain in

effect until the next program period, when the programmable fan setting will be

changed per the scheduled setting.
Dry Contact
On the programmable models, the dry contact that can be used for control of an

auxiliary device. The dry contact may be configured to be closed for a specific

number of minutes per hour for each period of the program schedule. This can

be used to operate a ventilator, damper, system blower, or other auxiliary device.

There are two terminals, D1 and D2.
On both the programmable and non−programmable models, when configured as

a dehumidify output, it will operate cooling equipment capable of dehumidify

function. When configured for dehumidification, the Rc terminal must be

connected to one of the dry contact terminals. The other dry contact terminal is

connected to the dehumidify terminal on the furnace or fan coil. This provides

power to energize the dehumidify terminal on the cooling equipment when the

dry contact is closed.
If it is desired to operate a ventilator or other device, the D1 and D2 terminals

can be connected directly to the equipment. This will provide a closed contact

for the specified number of minutes per hour. See Option 19.
If timed control of the system blower is required, the dry contact can be used for

this function. The G terminal can be connected to one of the dry contact

terminals with the other terminal being connected to Rc and/or Rh for timed

control of the fan. Note that this is not the same as programmable fan Option 30.

Advertising
This manual is related to the following products: