flashing is changed by using the UP/DOWN buttons. All changes made are

saved at the time of selection and will be saved in the event of the 3 minute

time−out or when installer exits from configuration menu.

Configuration Options —Selection

Option 01 — Equipment Type
Range: H2, A2, HP, AC, hh, h2, H, C
H2 — operates a two−speed heat pump with a fan coil
HP — operates a single−speed heat pump with a fan coil
A2 — operates a two−speed AC with a fan coil or furnace
AC — operates a single−speed AC with a fan coil or furnace
hh — operates a single−speed heat pump with a furnace
h2 — operates a two−speed heat pump with a furnace
H

— operates a heat−only system. Furnace or fan coil only;

no outdoor unit.

C

— operates a cool only−system. Outdoor AC unit with an

indoor fan coil with no strip heaters.

Default is H2.
Option 02 — Clean Filter Timer
Select hours of blower operation (heating, cooling, or fan) before CHECK

FILTER icon is displayed. With OF selected, icon will never come on, disabling

this feature. Time selection can range from 800 to 7200 hr by selecting numbers

1 through 9. (Time is 800 X number selected.) Default is 4 (3200 hr).
Recommended selections are disposable filter−800 to 2400 hr, media filter−2400

to 3200 hr, or electronic air cleaner−1600 to 2400 hr of blower operation. For

higher efficiency filter, please consult filter’s Installation Instruction for details.