setpoint is adjusted upward by 2% per degree of overcooling. For

example, a cooling setpoint of 76

_F/24_C and a dehumidify setpoint of

60% is equivalent to a cooling setpoint of 75

_F/24_C and a dehumidify

setpoint of 62%. This dehumidify setpoint change is internal to the

Thermidistat Control and is not shown on the display.

A06599

Fig. 17 − Auto Humidity

3. Dehumidify Off

Dehumidification can be turned off completely. This can be done without

changing existing setpoints.