temperature falls below 45

_F (7_C), the auxiliary heat will be allowed to turn on

and will continue to run until demand is satisfied.
Default is OF (off).
Option 09 — Heat Pump Lockout Temperature Balance Point (only
available when heat pump is used and when outdoor air temperature sensor
is present)
This selection is only available on Hybrid Heat systems. A Hybrid Heat system

is selected via the Option 1 Equipment Type configuration. Configurations

settings are: OF (off), 5, 10, 15, 20, 25, 30, 35, 40, 45, 50, 55.
OF (off) — the heating cycle will always start with heat pump heating.
5 to 55

_F (−15 to 13_C) — the outdoor temperature below which heat pump

operation is not allowed.
When emergency heat mode is selected, only auxiliary heat will operate.
Default is OF (off).
Option 10 — Reversing Valve
This selection is only available on heat pump systems. “O” terminal can be

configured to be energized in either heating mode or in cooling mode, depending

on heat pump operation. “O” is used to describe a heat pump system that

energizes its reversing valve in cooling. “B” is used to describe a heat pump

system that energized its reversing valve in heating.
H — Reversing valve output (O/W2/B) is energized when HEAT mode is

selected.
C — Reversing valve output (O/W2/B) is energized when COOL mode is

selected.
Default is C.