G. STEAM INFORMATION

It is your responsibility to have

All

steam plumbing connections made by a qualified

professional to assure that the installation is adequate and conforms with local and state

regulations or codes.

IMPORTANT:

Failure to comply with the requirements stipulated in the

manual can result in component failure, which will

VOID

THE WARRANTY.

NOTE:

The DA-475 is manufactured with a pneumatic (piston) damper

system, which requires an external supply of air (80 psi +/- 10 psi).

See Steam Damper Air System Connections Section H item 3.

1. STEAM REQUIREMENTS, High Pressure

A. Inlet ---- 2-1/2”inch supply line connection.

B. Return --- 1-1/4”inch return line connection.

Operating Steam Pressure, High Pressure

Maximum

125 psig

8.79 kg/sq cm

Minimum

100 psig

7.03 kg/sq cm

Heat Input (Normal Load)

60 Bhp

Consumption

(Approximate)

1,367 lbs/hr

~620 kg/hr

2. INSTALLATION INSTRUCTIONS

To insure that an adequate supply of steam is provided, be sure that the steam return lines

are sized and laid out as stipulated in this manual. Inadequate steam and steam return lines

or improper steam plumbing will result in poor performance and can cause component

failure. Clean, dry steam

must be

provided to the dryer.

IMPORTANT:

Steam coil failure due to water hammer by wet steam

VOIDS WARRANTY

.

A. The pressure of the condensate in the steam supply will cause water hammer and

subsequent heat exchanger (steam coil) failure. The steam supply connection into the

main supply line

must be

made with a minimum 10-inch riser. This will prevent any

condensate from draining towards the dryer.

B. The steam supply piping to the dryer

must include

a 12-inch rise along with a drip trap

and check valve. This will prevent any condensate from entering the steam coil.

C. Flexible hoses or couplings

must be

used. The dryer vibrates slightly when it runs and

this will cause the steam coil connections to crack if they are hard piped to the supply and

return mains.

D. Shut-off valves for each dryer

should be

installed in the supply, return, and drip trap

return lines. This will allow the dryer to be isolated from the supply and return mains if the

dryer needs maintenance work.