2. Series 154-A11NB OR 25 Drive System Soft Start

The soft start mechanism is simply a voltage-limiting device. Therefore, to be capable

of seeing just what is happening, connect the leads of a voltmeter to connections

T2 and T3, as shown in

Figure 1

Initial starting voltage should be 60 percent to 65 percent of motor nameplate voltage.

Soft start time should be approximately 5 to 7 seconds, as indicated in

Figure 2

The starting torque is dependent on the instantaneous RPM of the motor, which is

Directly proportional to the voltage the motor receives, as shown in

Figure 3,

If the starting voltage is too low, the motor will not have enough torque to turn the

Basket (tumbler). Therefore, it is important that the starting voltage be high enough to

Turn the basket (tumbler) and that the total starting time be short enough to reduce the

Chance of overloading the system and blowing the fuses.

The 60 percent to 65 percent of the nameplate voltage for starting voltage and the 5 to

7 second soft start time were developed by testing with both a fully laded basket

(tumbler) and an empty basket (tumbler). Therefore, any dryer adjusted as stated will

operate properly with any size load up to the rated capacity.

Figure 4

indicates the difference in the starting voltage necessary for

Various size loads between empty and full.