LogicPLUS-S Two-Wire Controller

6

6

Pump Start Relay/Fertigation Relay

When using a pump start relay, the relay shall be a 24 VAC coil with a maximum inrush of .35

amps and holding .25 amps. The relay will act as a slave to the magnetic relay to control the

pump motor. You can use up to a 5hp Hit Products pump start relay attached directly to the

relay terminal.
See diagram on page 44

Rain Sensor

The Rain Sensor terminal is located on the bottom right of the Controller board labeled

“RAin

OFF.” See Position 11 of the Programming Section of this Manual to Activate this feature.

note: Use only Rain Switches with “Dry Contacts” (No Power) connect the “Normally Closed”

contacts.

See diagram page 37

Multiple Controller installation

Install a separate ground rod for each controller. Do not connect the field wires of one controller

with those of another. Use slave or isolation relays if activating a common master valve.
See diagram page 39

Current Monitoring Feature

This Feature can be accessed in three dial positions: “Run,” “Semi/Manual/Program Clear”

and Test. The displayed number is in milliamps. This is useful when troubleshooting “Short

Line,” “Valve Short” or controller operation.

note: When accessed in the “Test” position a reduced power level is sent to the field, which will

result in a lower “Current Monitoring Number.”

Boost

This Feature increases power sent to the field over the Two Wire path and is to be used when

operating Multiple Valves at extended distance.

Accessory:

Hand held programmer. For Programming

Receivers away from the controller
See diagram page 41

Trouble Shooting unit (TSU) for Trouble Shooting both Controller and Receiver/ Wiring issues.

Warranty: Any Receiver returned for warranty must have the DBC-BR connection attached. If

the DBC-BR is unattached, warranty is void.