Hit Products LogicPLUS S 42/128 User Manual

Page 7

Advertising
background image

7

LogicPLUS-S Two-Wire Controller

7

LogicPLUS-S installation “do’s & don’ts”

For Warranty To Be Valid, installation Must Comply To All instructions Below

1. Use only LP-RP Receivers (Gray Molded Box) with the LogicPLUS-S Controllers (LP-42, LP-

128 and Uni-2 Plus).

dO nOT use the L-RP (Black Molded Box) Receivers with the Logic

PLUS-S Controllers.

dO nOT use the LP-RP (Gray Box) Receiver with the Logic 1, Logic 2,

Logic 3 or Uni-2 Controller.

2. Branching and Teeing of two wire path is permitted with LogicPLUS-S, but should be well

planned and minimized with care given using only waterproof DBC-BR splice kits.

All wire connection/splices are to be made in a valve box.

dO nOT “direct” bury

connection/splices.

3. LogicPLUS-S receivers must be directly attached to the 2 wire path; red wires to field wires,

black wires to solenoid (See #4).

4.

Wire Connections

A. All field wiring Connections of LogicPLUS-S Receiver Red Wires (1 each to each of field

wires) to field wires must use the enclosed DBC-BR splice kits. See instructions on back.

dO nOT USe PRe-FiLLed GeL TyPe WiRe nUTS.

B. All receiver to Valve Solenoid Connections must be waterproof, using “dry type” wire

connectors (Hit Products DBC series or 3M™ DBY/DBR series™) and/or soldered and then

installed in waterproof housings.

dO nOT USe PRe-FiLLed GeL TyPe WiRe nUTS.

5.

dO nOT install the LogicPLUS-S Controller, its Receivers or any LogicPLUS-S Field Wire

within 15 feet of any high voltage current that may cause electrical interference such as;

electrical panels, meters, pumps, equipment or controls.

6. Use with standard 24 VAC solenoids only.

dO nOT use any with low power/diode bridge type

solenoids.

7. Use different colored field wires for each wire in each two-wire path.

8. LogicPLUS-S provides 4 separate field outputs.

Line 1, Line 2, Line 3 and Line 4.

dO nOT mix the wiring.