Cub Cadet Z-Force S Series User Manual

Page 111

Advertising
background image

Electrical System

105

5d.

Interpretation:

If the stator fails either or both tests, it is likely to be bad.

If the stator fails the out put test, but passes the resistance test, there is a possibility that the magnets on
the rotor (flywheel) have lost their fields. This is theoretically possible, but extremely rare in practice.

It is necessary to remove the flywheel to test the magnets. If the magnets inside the flywheel will draw a
steel screwdriver to them, they are good. If not, the flywheel must be replaced.

6.

Regulator/rectifier check: See Figure 7.26.

6a.

Check the ground.

With the engine running and the stator leads re-
connected to the regulator/rectifier, perform a
ground-side voltage-drop test from the regula-
tor/rectifier to the engine block.

If the voltage reading is greater than 0.1 Volts
D.C., replace or properly fasten the ground wire
that connects the regulator/rectifier to the
engine block. Retest to confirm good connec-
tion.

6b.

Bench Test: See Figure 7.27.

Set a digital multi-meter to read on the X100

Ω

scale.

With the key OFF and the fuse removed, unplug
all the wires from the regulator/rectifier.

Remove the regulator/rectifier from the engine
(not strictly necessary, but provides easy
access).

Make the resistance tests described in the
accompanying table.

B+ is the D.C. terminal

A.C.1 is the A.C. terminal nearest B+

A.C.2 is the A.C. terminal furthest from B+

Figure 7.26

Figure 7.27

A.C.2 A.C.1 B+

Advertising