Retrieve Statistics Message

2.5. Retrieve Statistics Message

The data returned from the Retrieve Statistics message contains various counters. The Retrieve Statistics
message formats the data into 32-bit integers and returns data in an array of WORDs. The first WORD
contains the most significant word and the second WORD contains the least significant word.

Note: Some Modicon PLC programming software, such as Concept, requires one to be added to the address

offset. This is because their address range begins at 40001, while the address range on the DeviceMaster
UP begins at zero.

The following table displays the format of the Retrieve Statistics message.

The Retrieve Statistics messages have the following characteristics.

DeviceMaster UP Addressing for the

Statistics Modbus/TCP Messages

Serial Port

1

Serial Port

2

Serial Port

3

Serial Port

4

Access

Rule

Unit ID

255 (FF hex) 255 (FF hex) 255 (FF hex) 255 (FF hex) N/A

Statistics Address

1600

2600

3600

4600

Read Only

Index

Name

Data Type

Data Value(s)

Access Rule

1

Receive Byte Count

UDINT

0=default

Read only

2

Receive Packet Count

UDINT

0=default

Read only

3

Transmit Byte Count

UDINT

0=default

Read only

4

Transmit Packet Count

UDINT

0=default

Read only

5

Dropped Packet Count to PLC

UDINT

0=default

Read only

6

Parity Error Count

UDINT

0=default

Read only

7

Framing Error Count

UDINT

0=default

Read only

8

Overrun Error Count

UDINT

0=default

Read only

9

Unexpected Transmit Sequence
Number errors

UDINT

0=default

Read only

10

Invalid Modbus/RTU Device Responses UDINT

0=default

Read only

11

Modbus/RTU Device Timeouts

UDINT

0=default

Read only

12

Reserved

UDINT

0

Read only

Retrieve Statistics Message Description

Receive Byte Count

This attribute counts the number of bytes received on the serial port.

Receive Packet Count

This attribute counts the number of packets received on the serial port.

Transmit Byte Count

This attribute counts the number of bytes transmitted on the serial port.

Transmit Packet Count

This attribute counts the number of packets transmitted on the serial port.

Dropped Packet Count to PLC

This attribute counts the number of dropped receive packets on the serial
port intended for the PLC due to:

No STX byte(s) found

No ETX byte(s) found

Time-outs

Too large of packet

Receive buffer queue overflows

Parity Error Count

This attribute counts the number of packets with parity errors received on
the serial port.

Framing Error Count

This attribute counts the number of packets with framing errors received
on the serial port.