Chapter 3. Embedded Configuration Pages- 37

General Protocol Settings

3.3.3. General Protocol Settings

Use the General Protocol Settings area of the Edit
Serial Configuration
page to configure general
protocol settings for the serial port.

Rx Timeout
Between
Packets

Specifies the following information, once the start of a packet is received:

How long the DeviceMaster UP should wait (in milliseconds) before timing-out,
if the ETX Rx Detect length is one byte or two bytes and the ETX byte(s) are not
received.

The time to wait in milliseconds between serial packets if the ETX Rx Detect
length is set to none.

General Protocol Settings

Serial Port Protocol

This is the serial port protocol.

If you select Raw-Data, the port receives raw/ASCII type data.

If you select Modbus/RTU-to-Slaves, the serial port operates in Modbus/
RTU slave(s) mode.

If you select Modbus/ASCII-to-Slaves, the serial port operates in to
Modbus/ASCII slave(s) mode.

If you select Modbus/RTU-to-Master, the serial port operates in to
Modbus/RTU master mode.

If you select Modbus/ASCII-to-Master, the serial port operates in to
Modbus/ASCII master mode.

See

4.3. Display All Modbus Slave Devices

on Page 71 for information

about the Display Devices option.

Discard Rx Pkts
With Errors

This check box is selected by default, which means the DeviceMaster UP
discards serial packets with errors.

Clear the check box when you need to receive a serial packet with errors to
troubleshoot an issue.

Serial Configuration