2.

To assign a name to an input point, click in the Input Point Name field for the desired
input point and type the name to be assigned to the point. For example, for Input Point
Name 3, type Front Windows.

3.

The normal state for this input is normally-closed. If a window is broken the input will be
opened. For the Mode of Input Point 3, click on the N/C radio button.

4.

To assign a name to an output point, double click in the Output Point Name field for the
desired output point and type the name to be assigned to the point. For Output Point
Name 3, type Window Alarm.

5.

The resulting window should appear similar to Figure 184.

Figure 184 – Input/Output Point Definitions

Link Configuration

The Link Config tab allows an operator to customize the controller’s output responses to
events at the controller’s inputs (see Figure 185). Input points can be linked to output points,
allowing a change of state at an input to activate an output relay. Blank input and output point
name fields indicate those inputs and outputs are reserved by the controller for door control
and are not available for link assignment. The following rules apply for link configuration.

Up to 32 links can be defined per controller.

Any input can be used by all 32 links.

Inputs on a controller can only be linked to outputs on the same controller.

Multiple inputs can be linked to multiple outputs using OR/AND functions allowing an
operator to create complex input/output links.

Outputs on one controller can be hard-wired to inputs on other controllers.