Appendix 2 - ignition and firing sequence, App2 ignition and firing sequence, App2 – LAARS NeoTherm NTV (Sizes 150–285 MBTU/h) - Service Manual User Manual

Page 106

Advertising
background image

96

Service Manual NeoTherm 80 - NeoTherm 285

Appendix 2 - Ignition and Firing Sequence

App2

This is the basic operating sequence of the appliance whether there is a

DHW, or hydronic call for heat.
1. The unit receives a call for heat.
2. The controller does a check of the safety interlock chain.
3. The blower starts and the controller waits until it achieves prepurge

RPM.

4. The prepurge timer is started once the prepurge RPM is achieved.
5. The controller waits through a pre-ignition time of two seconds to

check the flame sensor operation and status. During this period an

intermittent spark can be seen.

6. The controller waits through a trial for ignition period of four seconds.

The direct spark ignition switches to constant spark for three sec-

onds, during which time the gas valve is open. For the last second of

the ignition period, direct spark is de-energized and the flame sensor

checks for established flame. If a flame is sensed, the control enters

“Run” to satisfy the demand. If flame is not established, the control

enters a retry, starting from step 2. If the flame has not been estab-

lished in the appropriate number of retries, the control will lockout

with a 109 error code.

7. The call for heat input disappears.
8. The gas valve shuts off.
9. The blower and pump continue to run through the overrun times to

purge the system.

Advertising
This manual is related to the following products: