Removing and Replacing the Flow Switch

The switch assembly includes two parts: a set of paddles

that extend into the water pipe, and a control box. See

Fig. B10-1.
Figure B10-2 shows the paddles that extend into the pip-

ing to detect the water flow.
The paddles are sized to match the amount of water

flowing through the system, so a flow switch installed in

a smaller system, with a smaller pipe, will have smaller

paddles, and a switch in a larger system will have larger

paddles. Keep this in mind if you need to replace one of

these switches.

Tools and equipment required:
• Medium-sized pipe wrench
• Sheet-metal shears - use a type that can make a

curved cut

• 100-grit sandpaper
• Pipe dope or Teflon® tape

Procedure:
1. Turn off power to the system. Use the main discon-

nect switch mounted above the front panel.

2. Isolate the boiler. Turn off the water shutoff valves

located upstream and downstream of the unit.

3. Drain the boiler. The drain valve is located near the

lower end of the heat exchanger.

4. Remove the cover from the control box for the

switch. Note the positions of the wiring connec-

tions, then disconnect the wires.

Fig. B10-1 - Flow switch installation (typical)

Fig. B10-2 - Metal paddles used to detect water flow

(typical)