B9 - testing the flow switch, Testing the flow switch – LAARS NeoTherm NTV (Sizes 150–285 MBTU/h) - Service Manual User Manual

Page 33

Advertising
background image

23

Service Manual NeoTherm 80 - NeoTherm 285

Testing the Flow Switch

The flow switch uses a set of paddles to sense water

flowing through the system. See Fig. B9-1. When

water is flowing, the switch is normally closed (N.C.).

If the water flow stops, the switch opens. After a “no

flow” condition, the switch resets itself immediately

and automatically.
Use a volt-ohmmeter to test the continuity through

the switch. With the paddles in the “relaxed” position

(standing upright), the switch should be open. Bend

the paddles slightly to one side, and you should see

the switch close.
Note - There is a seal at the base of the paddle as-

sembly. If this seal fails, it can allow water to leak

into the connection box. From there, the water can

flow through conduits to other parts of the control

system in the NeoTherm unit.
If it is necessary to replace the flow switch, see Sec-

tion B10 for instructions.

Fig. B9-1 – Typical flow switch

B9

Advertising
This manual is related to the following products: