A6 - unit is running, but building is still cold, Unit is running, but building is still cold – LAARS NeoTherm NTV (Sizes 150–285 MBTU/h) - Service Manual User Manual

Page 18

Advertising
background image

8

Service Manual NeoTherm 80 - NeoTherm 285

Unit is Running, But Building is Still Cold

A6

Yes

No

Clear it

Air inlet is

blocked?

Clean

Air intake

inside unit is

plugged?

Yes

No

Clean, blow out

(Gas/air mixture is correct,

but not enough gas/air

mixture is supplied.)

Dirty fan?

Yes

No

Burner and/or

heat exchanger

plugged?

Yes

See “Cleaning the Burner and Heat Exchanger”

Section C5

Advertising
This manual is related to the following products: