B4 - checking the low water cutoff switch (option), Checking the low water cutoff switch, See procedure b4 – LAARS NeoTherm NTV (Sizes 150–285 MBTU/h) - Service Manual User Manual

Page 28: Checking the low water cutoff switch (option)

Advertising
background image

18

Service Manual NeoTherm 80 - NeoTherm 285

Checking the Low Water Cutoff Switch (option)

Control resets?

Yes

No

Check for continuity from

base of switch to ground.

Has continuity?

No

Isolate the boiler and drain it.

Remove the probe.

Do not use Teflon tape on the

threads. (This would interrupt the continuity).

Use “pipe dope” instead.

Check for water in boiler?

Yes

Water present?

No

Yes

Check water supply, water pressure,

and auto makeup valve.

Reset low water cutoff control

Continued next page

Are you using ultra-pure water?

Ultra-pure water?

Yes

No

Ultra-pure water will not conduct

electrical current = false low water reading

OK - temporary condition

B4