Service Manual NeoTherm 80 - NeoTherm 285

Control Unit is in “Standby” Mode

In certain situations, the controller on this unit can go into “Standby”

mode. The Boiler pump is running, so the unit sees a “Call for heat.”

There is no lockout or hold, but something is preventing it from going to

“Run” mode.

A4

No

Check for:

- Call for heat?

- System is up to set-point temp. - no need

for more heat?

- If warm weather shutdown is enabled:

Outdoor air temperature too warm?

Normal

operating

condition?

No

Unit operates

normally?

Disconnect outdoor temp. sensor

Yes

See Section B29

“Troubleshooting Outdoor Reset”

No

Unit operates

normally?

Set Anti-Short-Cycle to minimum value

Yes

Correct settings for Anti-Short-Cycle

(continued)

Yes