Service Manual NeoTherm 80 - NeoTherm 285

Removing and Replacing the Low Water Cutoff Switch

The low water cutoff switch is designed to shut down

the unit if there is a low water condition. The control

includes two parts: a control box, and a probe which

reaches into the water piping.
Tools and equipment required:
• Small Phillips-head screwdriver (#1)
• Two medium-sized pipe wrenches or adjustable

wrenches

• 5/16” socket

Procedure - Removing or replacing the probe
1. Turn off power to the system. Use the main discon-

nect switch mounted above the front panel.

2. Isolate the boiler. Turn off the water shutoff valves

located upstream and downstream of the unit.

3. Drain the boiler. The drain valve is located near the

lower end of the heat exchanger.

4. Now you can remove the probe. Remove the top

panels on the unit so you can reach the probe.

5. Disconnect the probe wire (violet wire, red cap) and

the ground wire (green). See Fig. B6-1.

6. Use two pipe wrenches to unscrew the probe as-

sembly. See Fig. B6-2.

Turn the probe assembly counter-clockwise to

loosen it.

Note - Two sheet metal screws extend through the

plate around the probe assembly. You may have to

unscrew these a bit to allow enough space behind

the probe for the two wrenches.

7. To reassemble, reverse the procedure we have just

described. Keep these points in mind as you do this:
• Remember to re-tighten the two sheet metal

screws, if you unscrewed them to increase the

clearance for the wrenches.

• Use pipe dope or Teflon

®

tape on the threads on

the probe assembly.

• Be sure the red cap is seated firmly on the contact

at the end of the probe.

Fig. B6-1 - Removing the probe wires

You may need to unscrew

these screws to allow

clearance for the wrenches

behind the probe assembly.

Fig. B6-2 - Removing the probe

B6