B34 - pump fault, Pump fault – LAARS NeoTherm NTV (Sizes 150–285 MBTU/h) - Service Manual User Manual

Page 61

Advertising
background image

51

Service Manual NeoTherm 80 - NeoTherm 285

B34

Pump Fault

A problem with the circulator pump could appear as a

#79 error (Outlet High Limit). It could also appear as

a #63 error (LCI - Limit Control Input) if the interlock

loop includes a flow switch. The SOLA controller also

can display error #51 - Pump Fault.

No

No

Check for 120V at terminals

1 and 2 on TB5.

Pump is

getting power?

Disassemble and/or replace pump

Pump sounds

different?

No

Yes

Pump is

moving water?

No

Replace pump

Pump is

running?

Yes

Yes

Disassemble and/or replace pump