Short-Cycling - Fault #61

There are several conditions that can cause short-cycling, and some of

them can be caused by problems with the installation.
Start by checking the control settings for On Hysteresis and Off Hyster-

esis. If these are set too low, the system can short-cycle.
Short-cycling can occur if the piping in the hydronic loop is too small for

the capacity of the boiler. To put this another way, the boiler is produc-

ing enough heat, but the surrounding system is too small to move the

heat out of the boiler. The minimum firing rate on this unit is 20%. If the

hydronic loop cannot accept at least that amount of heat, the unit may

short-cycle. The solution to this problem is to use larger pipes in the

primary (boiler) loop, or to install a buffer tank.
A similar situation can occur if the boiler is connected to an indirect

DHW tank. If the output of the boiler is too large in relation to the size

of the tank, the system may short-cycle. You may be able to correct

this without changing the tank or piping. Be sure to use the aquastat on

the indirect tank to provide the “call for heat.” You can also try lowering

the DHW setpoint. If this does not work, you may have to change the

DHW tank. The tank should be large enough to accept the output of the

boiler when it is running at 20% of the maximum firing rate. The piping

between the tank and the boiler must also be large enough to allow for

adequate flow. Here’s the rule – The pipe diameter for the loop run-

ning to the tank must always be larger than the fittings on the tank.

For example, if the fittings on the tank are ½” dia., you must use ¾” dia.

or larger piping for the loop.

On systems using anti-freeze –
This can occur if the concentration of anti-freeze is too high. At concen-

trations above 35%, localized boiling can occur, and this can produce

noise.

A9

Unit is Noisy

A10