Removing and replacing the pressure relief valve – LAARS NeoTherm NTV (Sizes 150–285 MBTU/h) - Service Manual User Manual

Page 58

Advertising
background image

48

Service Manual NeoTherm 80 - NeoTherm 285

Removing and Replacing the Pressure Relief Valve

If the system pressure exceeds the relief valve setting,

the pressure relief valve is designed to open and release

the excess pressure and water. Note - This type of valve

is designed to relieve a limited number of times during

its life cycle, so it is not a good idea to “test” the valve by

tripping the small metal handle on top. Sometimes when

this type of valve is opened, it will not re-seat correctly,

causing a slow leak. If this happens, and the valve can-

not be cleared, it must be replaced.

Tools and equipment required:
* Plumber’s torch, solder, and flux
• Two pipe wrenches
• Pipe dope or Teflon® tape

Procedure:
1. Turn off power to the system. Use the main discon-

nect switch mounted above the front panel.

2. The pressure relief valve is mounted on a pipe that

extends up a few inches above the top panel of the

NT unit.

Fig. B31-1 - Pressure relief valve (typical)

Note -

Normally a drain pipe

would run from here to

within 6” of the floor.

3. Disassemble and remove the drain pipe.
4. Unscrew the valve from the vertical pipe using the two pipe wrenches.
5. The replacement valve must be the correct size and capacity to match the size

of the NT unit. Check the old valve for two important numbers:

• The capacity of the old valve, listed in BTU

• The relief pressure of the old valve, listed in p.s.i.

These numbers will be marked on the body of the valve. Check for this before

you get a replacement.

For example, a 105 NT unit (105,000 BTU/hr) might have a valve with ratings of

535,000 BTU and 30 p.s.i.

The replacement valve must have ratings for both BTU and psi which are the

same as or higher than the ratings on the old valve

6. Wrap a piece of Teflon® tape around the threads on the end of the vertical pipe.

Install the new valve using the two pipe wrenches.

7. Reassemble the drain pipe.
WARNING! Always re-install the drain pipe. If the pressure relief valve were

to open without the drain pipe in place, the boiling water could shoot out, caus-

ing personal injury or property damage. Most plumbing codes call for the drain

pipe to extend straight down to a point about 6” above the floor. Check your

local code.