B28 - testing the temperature sensors, Testing the temperature sensors, If the blower is running, and the unit does not – LAARS NeoTherm NTV (Sizes 150–285 MBTU/h) - Service Manual User Manual

Page 55: Fire, go to section b28 - “testing the temperature, Sensors

Advertising
background image

45

Service Manual NeoTherm 80 - NeoTherm 285

4. The outlet water temperature sensor is mounted in the shoulder of the heat

exchanger assembly, just above the point where the water outlet pipe is at-

tached to the heat exchanger. (The outlet pipe is marked with a label on top of

the unit.) Remove the top panels on the unit so you can reach the temperature

sensor.

5. Unplug the wiring connector (four wires). The connector is locked in place by a

“squeeze tab.” Press on the tab to release the connector.

6. Unscrew the sensor using the 14 mm socket or a crescent wrench. Turn

counter-clockwise to unscrew the part.

7. To reassemble, reverse the process we have just described. Be sure to use

pipe dope or Teflon® tape on the threaded part of the sensor.

Removing and Replacing the Outlet Water Temperature Sensor

(continued)

Testing the Temperature Sensors

The temperature sensors used in this unit are devices called “thermis-

tors.” The electrical resistance across a thermistor drops as the tem-

perature rises. The table below shows some typical resistance readings

at different temperatures.
There are three temperature sensors mounted directly on the NT unit:
• Inlet water temperature sensor
• Combined outlet water temperature sensor and water temperature

high limit (duplex sensor)

• Stack sensor (duplex sensor)
There are up to three more sensors mounted at remote locations:
• System sensor
• DHW sensor (if installed)
• Sensor for Outdoor Reset function (if installed)
Each “duplex” sensor assembly actually uses two thermistors. The con-

trol module compares the readings of the two. If the difference becomes

greater than allowed, the controller declares a lockout and prevents the

NeoTherm unit from firing.
To check a thermistor, unplug the sensor wires and check the resistance

through the thermistor using a volt-ohmmeter. Note the temperature of

the part, and check the resistance against the table. If there is an open-

circuit or no resistance at all, replace the part.
The connector for a “duplex” sensor will include four pins. Two of these

run to one thermistor, and two go to the other. You should see the same

resistance reading on both of the thermistors in the assembly.

°F

±°F

Ohms

-22

1.6

176.1 kΩ

-4

1.6

96.7 kΩ

14

1.6

55.2 kΩ

32

1.6

32.6 kΩ

50

1.6

19.9 kΩ

68

1.6

12.5 kΩ

77

1.6

10.0 kΩ

86

1.6

8.0 kΩ

104

1.4

5.3 kΩ

122

1.4

3.6 kΩ

140

1.4

2.4 kΩ

158

1.6

1.7 kΩ

176

1.8

1.2 kΩ

194

2.0

912 Ω

212

2.2

674 Ω

230

2.5

506 Ω

248

2.7

384 Ω

266

2.9

296 Ω

284

3.1

230 Ω

302

3.2

181 Ω

Table B28-1 - Thermistor Resistance Chart

B27

cont.

B28

Advertising
This manual is related to the following products: